PW3360 : CLAMP ON POWER LOGGER
Product Descriptions
Measurement line & number of circuits : 50/60 Hz, Single phase 2 wires (1/2/3 circuits), Single phase 3 wires (1 circuit), Three phases 3 wires (1 circuit), Three phases 4 wires (1 circuit), Current only: 1 to 3 channels
Measurement items : Voltage RMS, current RMS, voltage fundamental wave value, current fundamental wave value, voltage fundamental wave phase angle, current fundamental wave phase angle, frequency (U1), voltage waveform peak (absolute value), current waveform peak (absolute value), active power, reactive power (with lag/lead display), apparent power, power factor (with lag/lead display) or displacement power factor (with lag/lead display), active energy (consumption, regeneration), reactive energy (lag, lead), energy cost display, active power demand quantity (consumption, regeneration), reactive power demand quantity (lag, lead), active power demand value (consumption, regeneration), reactive power demand value (lag, lead), power factor demand, pulse input
[PW3360-21 only]: Harmonic voltage level, harmonic current level, harmonic power level, content percentage, phase angle, total harmonic distortion (THD-F or THD-R), up to 40th order
Voltage ranges : 600 V AC (Effective measurement range: 90.00 V to 780.00 V)
Current ranges :500.00 mA to 5.0000 kA AC (depends on current sensor in use), 50.000 mA to 5.0000 A AC (Leak clamp on sensor only)
Power ranges : 300.00 W to 9.0000 MW (depends on voltage/current combination and measured line type)
Basic accuracy : Voltage : ±0.3% rdg. ±0.1% f.s
Current : ±0.3% rdg. ±0.1% f.s. + clamp sensor accuracy
Active power : ±0.3% rdg. ±0.1% f.s. + clamp sensor accuracy (at power factor = 1)
Save destination : SD memory card, or internal memory at real time