Galltec L Series with RS232 / RS485

Product Descriptions
Designs available: Duct version, Wall mounting, Rod-shaped, Room version
• IP 65 with PTFE sintered filter ZE05
• Sensor tube Ø 12 mm
• Output signals available:
• RS232 or RS485 MODBUS RTU
• Operating voltage: 6…30 V DC
Special version: sealing against vibrations or condensation
Accuracy:
Humidity: ± 3% rh 30…80 % rh at 10…40 °C
Temperature ± 0,8 K 10…40 °C
Economical transmitters of the L Series are primarily optimized for ambient room conditions and are very well suited to help control energy costs in HVAC and building automation applications. Thanks to their high-quality manufacturing, these transmitters can also be used in industrial settings under moderate conditions.

  Two designs   duct version (LK)
  wall mounting (LW)
  Different physical outputs   humidity and temperature and all hx values
  Output signals   RS232 with ASCII protocol
  RS485 with Modbus RTU protocol
  Special versions   sealing for increased requirements, e.g. condensation sealing against vibrations
  Filter   protective basket ZE07 (IP 00)
  filter with membrane ZE08 (IP30)
  PTFE sintered filter ZE05 (IP65)
  Measuring medium   air, pressureless, non-aggressive, non-condensing
  Min. air speed   0.5 m/s
  Operating temperature   -40…+80°C
  Storage temperature   -40…+85°C
  Degree of protection of measuring head
     with protective basket ZE07   IP00
     with membrane filter ZE08   IP30
     with PTFE sintered filter ZE05   IP65
  Degree of protection housing   IP65
  Material of housing   PC (light grey / white)
  Humidity
  sensing element   calibrated sensor chip calHT
  output range   0…100 %rh
  accuracy   30…80 %rh    at 10…40°C   ±3 %rh
  < 30 %rh or > 80 %rh    at 10…40°C   ±5 %rh
  Influence of temperature   < 10°C or > 40°C    typ. ±0.06 %rh/K
  Temperature 
  sensing element   calibrated sensor chip calHT
  output ranges   -40…+85°C
  Accuracy  
      at 10…40°C   ±0.8 K
     <10°C and >40°C   see diagramm
  Electrical data
  Power supply, external   6…30 VDC
  Max. transfer distance RS232/RS485   15m/1000 m
  Consumption of electronics   < 1,0 mA
  Directive about electromagnetic compatibility 2014/30/EU
  DIN EN 61326-1   issue 07/13
  DIN EN 61326-1-2-3   issue 07/13

หากท่านสนใจกรุณากรอกรายละเอียด

Related Searches:

testo 6383 – differential pressure transmitter for cleanrooms

monitoring differential pressure in the 10 Pa to 10 hPa measuring range, very high precision at the lowest pressurescleanroom wall

testo 6681 – Temperature/humidity transmitter for critical

Maximum measuring accuracy up to ±(1.0 + 0.007 x reading) Reliable and long-term stable humidity sensor

testo 6651 – Temperature/humidity transmitter for critical climates

High measuring accuracy up to ±(1.7 + 0.007 x reading) Reliable and long-term stable humidity sensor

testo 6621 – Temperature and humidity transmitter

Highly accurate testo humidity sensor with long-term stability (±2.0% RH), Adjustment without dismantling the transmitter

Chat with us on LINE

เราใช้คุกกี้เพื่อพัฒนาประสิทธิภาพ และประสบการณ์ที่ดีในการใช้เว็บไซต์ของคุณ คุณสามารถศึกษารายละเอียดได้ที่ นโยบายความเป็นส่วนตัว และสามารถจัดการความเป็นส่วนตัวเองได้ของคุณได้เองโดยคลิกที่ ตั้งค่า

Privacy Preferences

คุณสามารถเลือกการตั้งค่าคุกกี้โดยเปิด/ปิด คุกกี้ในแต่ละประเภทได้ตามความต้องการ ยกเว้น คุกกี้ที่จำเป็น

Allow All
Manage Consent Preferences
  • คุกกี้ที่จำเป็น
    Always Active

    ประเภทของคุกกี้มีความจำเป็นสำหรับการทำงานของเว็บไซต์ เพื่อให้คุณสามารถใช้ได้อย่างเป็นปกติ และเข้าชมเว็บไซต์ คุณไม่สามารถปิดการทำงานของคุกกี้นี้ในระบบเว็บไซต์ของเราได้

  • คุกกี้เพื่อการวิเคราะห์

    คุกกี้ประเภทนี้จะทำการเก็บข้อมูลการใช้งานเว็บไซต์ของคุณ เพื่อเป็นประโยชน์ในการวัดผล ปรับปรุง และพัฒนาประสบการณ์ที่ดีในการใช้งานเว็บไซต์ ถ้าหากท่านไม่ยินยอมให้เราใช้คุกกี้นี้ เราจะไม่สามารถวัดผล ปรังปรุงและพัฒนาเว็บไซต์ได้

Save